ADC-- Microprocessor error CPF-- High pressure transducer failure, out of range EPF-- Low pressure transducer failure, out of range REF-- Refrigerant leak Ð low pressure CPnc-- High pressure transducer failure, pressure unchanged EPnc-- Low pressure transducer failure, pressure unchanged CFC1-- Compressor 1 failure-- wrong rotation CFC2-- Compressor 2 failure-- wrong rotation EWTH-- Return water feeler failure --short-circuit EWTL-- Return water feeler failure --not connected LWTC-- No outlet water temperature change LWTH--Outlet water feeler failure-- short-circuit LWTL-- Outlet water feeler failure-- not connected LWLH-- Compressors delivery temperature feeler failure --short-circuit DISL-- Compressors delivery temperature feeler failure --not connected OATH-- Air temperature feeler failure --short-circuit OATL-- Air temperature feeler failure --not connected OCTL-- Battery temperature feeler failure --not connected HPP-- First high pressure protection --compressor stop HP-- High pressure protection --auto reset 3 times HPC-- High pressure protection Ð high pressure switch LP-- Low pressure protection DIS-- Compressors delivery temperature too high LO-- Outlet water temperature too low HI-- Inlet water temperature too high FS-- Differential water flow or pressure switch CF1-- Compressor 1 thermal load protection CF2-- Compressor 2 thermal load protection OF1-- Fans thermal load protection PF-- Pump thermal load protection LOu-- Low water volume EEP-- Microprocessor error JUMP-- Wrong DIP configuration --check DIP ConF-- Wrong configuration